Product Overview
iAeris 2X
IAQ Monitoring System
INDOOR AIR QUALITY MONITOR
(Model No.: iAeris 2X)
Made in Taiwan
Descriptions
The iAeris is the real time monitor of multiple indoor air quality indicator. This monitor can provide the status of temperature, humidity, CO2, CO, particulate matter (PM10), PM2.5, total volatile Organic compound (TVOC ), formaldehyde (HCHO) and Ozone(O3) at the same time. Select the parameters you wanted to monitor.
Feature
- Compact design around 6” size and Wall-mount available.
- Professional mechanism structure design for air flow convection can effectively detect the ambient air quality.
- The professional algorithm of sensing data is reliable and calibrate before shipment.
- Optional various communication interface with WiFi, BLE and RS485.
- The current and historical data could be recorded and downloaded by cloud.
Applications
- Living room
- Lobby
- Hospital
- School
- Smart home
- Bedroom
- Office
- Station
- Department store
- Internet of Things
Sensors Specifications:
- Temperature (standard)
- Range: -40℃~125℃
- Resolution: 0.1℃
- Operating Principle: CMOSems
- Response time: <30sec
- Warmup time: <60sec
- Relative Humidity (standard)
- Range: 0~100%RH
- Resolution: 0.1%
- Operating Principle: CMOSems
- Response time: <30sec
- Warmup time: <60sec
- Carbon Dioxide (CO2) (standard)
- Range: 400 ~ 5,000ppm
- Resolution: 1 ppm
- Operating Principle: NDIR
- Response time: <120sec
- Warmup time: <60sec
- Carbon Monoxide (CO) (option)
- Range: 0 ~ 1,000ppm
- Resolution: 1 ppm
- Operating Principle: Electrochemistry
- Response time: <60sec
- Warmup time: <60sec
- Dust (PM2.5) (option)
- Range: 1 to 500μg/m3
- Resolution: 1 μg/m3
- Operating Principle: Optics
- Response time: <10sec
- Warmup time: 300sec
- Dust (PM10) (option)
- Range: 1 to 500μg/m3
- Resolution: 1 μg/m3
- Operating Principle: Optics
- Response time: <10sec
- Warmup time: 300sec
- Total Volatile Organic Compound (TVOC) (option)
- Range: 0.13 ~ 2.5 ppm
- Resolution: 0.01 ppm
- Operating Principle: MEMS
- Response time: <10sec
- Warmup time: 300sec
- Formaldehyde (HCHO) (option)
- Range: 0.01 ~ 5ppm
- Resolution: 0.01 ppm
- Operating Principle: Electrochemistry
- Response time: <30sec
- Warmup time: 300sec
- Ozone (O3) (option)
- Range: 0 ~ 5.00 ppm
- Resolution: 0.01 ppm
- Operating Principle: Electrochemistry
- Response time: <60sec
- Warmup time: <600sec
* You have the choice to select the parameters you wanted to monitor. The basic model come with Temperature, Humidity and CO2)
General Specifications:
- Sampling method: Real Time
- Data interfaces:
- RS485(Modbus-RTU) (option)
- WiFi(Modbus-TCP & JSON) (option)
- BLE4.0 (option)
- Operating Temperature: -10°C to 50°C (14°F to 122°F)
- Operating Humidity: < 90%RH, non-condensing
- Power: 5V DC, 1.0A or 12-24V DC, 0.5A
- Size: 158mm(L) x 115mm(W) x 32mm(H)